Solar Photovoltaic (PV)
Surge Protection for:
 
M200

Main Service
Distribution Panel


200kA
8/20us
Citel’s M200 models are designed for service entrance and remote locations. These heavy-duty, hardwired devices are provided in NEMA 4 enclosures and have LED indicators per phase plus N-G abnormal voltage indication, remote contacts,  and audible alarm. These hybrid devices provide protection against transient surges for all modes (L-L, L-G, L-N and N-G) and EMI/RFI noise filtering.

Part Numbers:


M200
   
DS150E/G

 Inverter
AC Output
(Heavy Duty)


15ka
10/350us

Citel’s DS152E/G are designed to protect the inverters AC output for a utility-interactive PV system. The DS152E is designed to withstand 15kA (10/350us) which is representative of a direct lightning strike.  It provides uncompromising protection in even the most demanding applications.

Part Numbers:

DS152E-120/G
DS153E-300/G


*Available for systems up to 480 VAC.

     
DS40S/G

 Inverter
AC Output
(General Duty)


40ka
8/20us

Citel’s DS40S/G are designed to protect the inverters AC output for a utility-interactive PV system. The DS40S/G is designed to withstand 40kA (8/20us) which is representative of an indirect lightning strike or induced over voltage.

Part Numbers:

DS42S-120/G
DS43S-400/G


*Available for systems up to 480 VAC.

     
DS60PV

 Inverter
DC Input
(Heavy Duty)


12.5ka
10/350us
Citel’s DS60PV are designed to protect the inverters DC input for a utility-interactive PV system. The DS60PV is designed to withstand 12.5kA (10/350us) which is representative of a direct lightning strike. 

Part Numbers:

DS60PV-500
DS60PV-1000
     
DS50PV

Inverter
DC Input
(General Duty)


40ka
8/20us
Citel’s DS50PV are designed to protect the inverters DC input for a utility-interactive PV system. The DS50PV is designed to withstand 40kA (8/20us) which is representative of an indirect lightning strike and is designed with replaceable modules. 

Part Numbers:

DS50PV-500
DS50PV-1000

 

   
     
DS50PV

Solar PV Array
Combiner Box


40ka
8/20us
Citel’s DS50PV are designed to protect the Solar Panel Array and Blocking Diode at the Solar PV Array Combiner box for a utility-interactive PV system. The DS50PV is designed to withstand 40kA (8/20us) induced transient surges and is designed with replaceable modules. 

Part Numbers:

DS50PV-500
DS50PV-1000

 

   
DLA  Communications

20kA
8/20us
Citel DLA series are designed to protect data signal lines for a utility-interactive PV system. They will provide 2-wire protection for sensors, modems and data acquisition equipment, i.e. 4-20mA, RS-485, PT100. 

The DLA combine a surge arrester gas tube and fast clamping diode technology that exhibits a fast response time (< 1 ns) and a high power-handling capability (20kA – 8/20 ms waveform). Automatically reset after each lightning surge or electrical transient.

Features a modular presentation that allows for quick and easy maintenance without any re-wiring.

Part Numbers:


DLA-06D3 (PT100, RS-485)
DLA-24D3 (4-20mA, 24V Power Supply)
DLA-48D3 (48V Power Supply)
DLA-170 (Modem)

 

   
DS210-DC

 Charge
Controller


2kA
8/20us
Citel DS210DC series are designed to protect 12V, 24V or 48V DC power lines for a PV system. They will provide 2-wire (+. - and ground) protection for the charge controller.  DS210DC automatically reset after each lightning surge or electrical transient. Features a modular presentation that allows for quick and easy maintenance without any re-wiring.

Part Numbers:


DS210-24DC (12V, 24V Power Supply)
DS210-48DC (48V Power Supply)
 
     
   
P100S-350

Equipotential Bonding


150kA
8/20us

Citel's P100 Series is designed to equalize the potential of non-grounded metallic structures during surge events. During normal operation the spark gap provides isolation between the metallic element and the systems earth ground. However, when a transient occurs, it quickly provides a conduction path to equalize the system and then automatically goes back to isolation. The P100S can conduct very large lightning events up to 150kA 8/20us and 60kA 10/350us.

Part Numbers:


P100S-350

   
   
                     